8.2.12 Low Cutoff
The low cutoff is the function to set the current output to zero forcefully if the flow rate is equal to or
less than the low cutoff value set near 0%.
The low cutoff value can be set within the range 0 to 10% in increments of 0.1%.
You can check or change the low cutoff value as described below.
The following is an example to change the low cutoff value from 1.0% to 3.0%.
Switch operation
Display example
Description
Select "CUT VAL" from the setting item
selection menu.
The currently set low cutoff value (01.0%
in this example) appears.
Then push .
The switches at the bottom change.
( are shown.)
At the same time, the cursor appears.
Push to move the cursor to the
desired digit and push to change the
number of the digit.
When you push , a message appears
to confirm whether the setting is OK or not.
If OK, push . If you want to redo the
setting, push .
Pushing cancels the setting operation
and exits the setting screen.
Note: If you try to set a value exceeding 10.0%, HIGH OVER SPEC error appears and the
value returns to the previous value. Set a value again.