GENERATOR OUTPUTS

A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the voltage selector switch (Figure 14). To obtain some of
the voltages as listed in Table 7 (see below) will require a
fine adjustment using the voltage regulator (VR) control
knob located on the control panel.

The voltage selector switch (Figure 14) is located above
the output terminal panel’s Hard Wire Hook-up Panel. It
has been provided for ease of voltage selection.
Figure 14. Voltage Selector Switch

The voltage selector switch has a locking button to protect
the generator and load from being switched while the
engine is running. To lock the voltage selector switch, press
and hold the red button located at the bottom of the switch.

 change the position of the voltage selector
switch while the engine is running.  place
circuit breaker in the OFF position before selecting
voltage.








208V 220V 240V 416V 440V 480V
 120V 127V 139V 240V 254V 277V



120V
Line-Neutral
N/A N/A
240V
Line-Line
N/A N/A
Generator Amperage
Table 8 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed..

The load capability of the GFCI receptacles is directly
related to the voltage being supplied at either the output
terminals or the 2 twist lock auxiliary receptacles.
Table 9 and Table 10 show what amount of current is
available at the GFCI receptacles when the output terminals
and twist lock receptacles are in use. Be careful that your
load does not to exceed the available current capability at
the receptacles.

 
1Ø 120 Volt 333.3 amps (4 wire)
1Ø 240 Volt 166.7 amps (4 wire)
3Ø 240 Volt 361 amps
3Ø 480 Volt 180 amps

KW in Use



1Ø 240/120V
GFCI Duplex
5-20R 120V
87.0 0
85.8 5 amps/receptacle
84.6 10 amps/receptacle
83.4 15 amps/receptacle
82.2 20 amps/receptacle
Table 10. 




3Ø 240/480V
GFCI Duplex
5-20R 120V
150
0 amps/receptacle
146
5 amps/receptacle
142
10 amps/receptacle
138
15 amps/receptacle
133
20 amps/receptacle