DIMENSIONAL DRAWING — 558D090-150
UNIT
558D
CORNER WEIGHT* DIMENSIONS
A B C D ‘‘H’’ ‘‘J’’ ‘‘K’’
Lb Kg Lb Kg Lb Kg Lb Kg Ft-in. mm Ft-in. mm Ft-in. mm
090 164 74 140 64 208 94 243 110 1-2
7
⁄
8
378 3-5
5
⁄
16
1050 2-9
11
⁄
16
856
102 165 75 141 64 209 94 245 111 3-3
7
⁄
8
1013 3-5
5
⁄
16
1050 2-9
11
⁄
16
856
120 199 90 170 77 252 114 294 134 2-5
7
⁄
8
759 4-1
5
⁄
16
1253 3-0
3
⁄
8
924
150 202 92 172 78 256 116 300 136 1-2
7
⁄
8
378 4-1
5
⁄
16
1253 3-0
3
⁄
8
924
*Weights are for unit only (aluminum plate fins)and donot includeoptions orcrating.
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of gravity.
3. Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Bottomto combustible surfaces (whennot using curb)0 inches. On horizontaldischarge units with
electric heat 1 in. clearance toductwork for1 ft.
b. Condensercoil,for properairflow,36 in.oneside,12in.theother.Thesidegettingthegreaterclear-
ance is optional.
c. Overhead, 60 in. to assure proper condenser fan operation.
d. Between units, control box side, 42 in. per NEC(National ElectricalCode).
e. Between unit and ungrounded surfaces, control box side, 36in. perNEC.
f. Between unit and block or concrete walls and other grounded surfaces, control box side,
42 in. per NEC.
g. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil and combustible surfaces as stated in
Notes 5a and b, a removablefence orbarricade requiresno clearance.
7. Unitsmaybeinstalledoncombustiblefloorsmadefromwood orclassA,B,orCroofcoveringmaterial.
8. The verticalcenter of gravity is 1Ј-7
1
⁄
2
Љ [495] for 090and 102, 2Ј-0Љ [610] for 120and 150 up from the
bottom of the base rail. Horizontalcenter ofgravity isshown.
BOTTOM POWER CHART, THESE HOLES REQ’D FOR USE
WITH ACCESSORY PACKAGES — CRBTMPWR001A00
(
1
⁄
2
؆,
3
⁄
4
؆) OR CRBTMPWR002A00 (
1
⁄
2
؆,1
1
⁄
4
؆)
THREADED CONDUIT
SIZE
WIRE SIZE
REQ’D HOLE
SIZES (MAX.)
1
⁄
2
؆ 24 v
7
⁄
8
Љ [22.2]
3
⁄
4
؆ POWER† 1
1
⁄
8
Љ [28.4]
1
1
⁄
4
؆ POWER† 1
3
⁄
4
Љ [44.4]
†Select either
3
⁄
4
Љ or 1
1
⁄
4
Љ for power, depending on wire size.
CONNECTION SIZES
A 1
3
⁄
8
Љ Diameter [35] Field Power SupplyHole
B 2
1
⁄
2
Љ Diameter [64] Power Supply Knockout
C 1
3
⁄
4
Љ Diameter [44] Charging Port Hole
D
7
⁄
8
Љ Diameter [22] Field Control WiringHole
E
3
⁄
4
Љ-14 NPT Condensate Drain
F 2Љ Diameter [51] Power Supply Knockout
7