DIMENSIONAL DRAWING HORIZONTAL AND VERTICAL ROOF CURBS
AND HORIZONTAL ADAPTER 559F180-300
ACCESSORY
PACKAGE NO.
CURB
HEIGHT
DESCRIPTION ‘‘A’’ ‘‘B’’ ‘‘C’’
308450-201
1Ј-2Љ
(305)
Standard Curb
14Љ High
———
308450-202
2Ј-0Љ
(610)
Standard Curb
for Units Requiring
High Installation
———
308450-203
2Ј-0Љ
(610)
Horizontal Supply
and Return Curb
5Ј-6Љ
(1676)
0Ј-2
1
2
Љ
(64)
1Ј-6Љ
(457)
389210-201
1Ј-11Љ
(584)
Pre-Assembled,
High-Static
Horizontal Adapter
6Ј-2Љ
(1880)
0Ј-6
1
4
Љ
(159)
1Ј-2
5
8
Љ
(371)
LEGEND
COMP SECT. Compressor Section
NOTES:
1. Roof curb accessory is shipped unassembled.
2. Insulated panels,
1
2
-in. thick neoprene-coated,
2 lb density.
3. Dimensions in ( ) are in millimeters.
4. Direction of airflow.
5. Roof curb: 18 gage steel.
6. Attach all ductwork to roof curb.
NOTE: To prevent the hazard of stagnant water build-up in the drain
pan of the indoor-air section, unit can only be pitched as shown.