Bryant 558D Automobile User Manual


 
AIR DELIVERY 558D036-150 HORIZONTAL DISCHARGE UNITS (cont)
558D072 (6 TON)
AIRFLOW
(Cfm)
Standard Belt-Drive Motor
External Static Pressure (in. wg)
0.1 0.2 0.4 0.6 0.8
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1800 765 0.45 487 821 0.51 532 923 0.65 638 1019 0.81 843 1099 0.96 883
1900 802 0.45 539 854 0.58 585 953 0.73 700 1046 0.90 835 1126 1.06 965
2000 840 0.60 600 888 0.66 646 984 0.82 771 1073 0.99 907 1154 1.16 1047
2100 878 0.69 669 923 0.75 716 1015 0.91 843 1101 1.08 981 1182 1.27 1140
2200 916 0.78 739 958 0.85 795 1046 1.01 924 1129 1.19 1072 1209 1.39 1241
2300 954 0.89 827 993 0.96 883 1079 1.13 1022 1160 1.31 1173 1237 1.51 1344
2400 993 1.00 916 1029 1.07 973 1112 1.25 1123 1190 1.43 1275 1264 1.63 1447
2500 1031 1.13 1022 1066 1.20 1081 1145 1.39 1241 1220 1.57 1396 1292 1.77 1569
2600 1070 1.26 1131 1103 1.34 1199 1179 1.52 1353 1251 1.71 1517 1322 1.92 1700
2700 1109 1.41 1258 1140 1.48 1318 1212 1.67 1482 1283 1.87 1656 1352 2.09 1849
2800 1148 1.57 1396 1177 1.64 1456 1246 1.83 1621 1316 2.04 1805 1383 2.26 1997
2900 1188 1.74 1543 1215 1.81 1604 1281 2.00 1770 1349 2.22 1962 1413 2.44 2154
3000 1227 1.92 1700 1253 2.00 1770 1316 2.19 1936 1382 2.42 2136 1444 2.63 2317
558D072 (6 TON) (cont)
AIRFLOW
(Cfm)
Standard Belt-Drive Motor
External Static Pressure (in. wg)
1.0 1.2 1.4 1.6
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1800 1178 1.14 1031 1249 1.32 1182 1316 1.52 1353 1382 1.72 1526
1900 1201 1.23 1106 1274 1.43 1275 1338 1.62 1439 1402 1.83 1621
2000 1226 1.33 1990 1297 1.53 1361 1363 1.73 1534 1424 1.94 1718
2100 1252 1.45 1292 1320 1.64 1456 1388 1.85 1639 1448 2.07 1831
2200 1280 1.58 1404 1345 1.77 1569 1410 1.97 1744 1473 2.20 1945
2300 1309 1.71 1517 1372 1.91 1691 1434 2.11 1866 1496 2.34 2067
2400 1336 1.85 1639 1400 2.06 1823 1459 2.26 1997 1519 2.48 2188
2500 1363 2.00 1770 1428 2.22 1962 1486 2.43 2145 1543 2.65 2335
2600 1390 2.15 1901 1456 2.38 2102 1514 2.61 2300 1569 2.83 2487
2700 1418 2.31 2041 1483 2.56 2257 1543 2.80 2462
2800 1446 2.48 2188 1510 2.73 2403
2900 1476 2.67 2352 1537 2.92 2562
3000 1506 2.88 2529
LEGEND
Bhp Brake Horsepower Input to Fan
FIOP Factory-Installed Option
Watts Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)
2. indicates field-supplied motor and drive are required.
3.
indicates maximum usable bhp/watts.
4. Maximum usable watts input is 2120 and maximum continuous bhp
is 2.40. Extensive motor and electricaltesting onthese unitsensures
that the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
5. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
6. Use of a field-supplied motor may affect wire sizing. Contact your lo-
cal representative for details.
7. Standard motor drive range: 1070 to 1460 rpm. All other rpms re-
quire field-supplied drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
37