Bryant 558D Automobile User Manual


 
AIR DELIVERY 558D036-150 HORIZONTAL DISCHARGE UNITS (cont)
558D048 (4 TON)
Airflow
(Cfm)
Standard Direct-Drive Motor
Low Speed High Speed
208 v 230, 460, 575 v 208 v 230, 460, 575 v
ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts
1200 0.93 0.41 458 0.97 0.45 506 1.04 0.51 572 1.09 0.56 632
1300 0.86 0.42 471 0.90 0.46 521 0.96 0.52 589 1.02 0.58 651
1400 0.78 0.45 503 0.84 0.49 556 0.90 0.54 616 0.96 0.60 681
1500 0.73 0.47 536 0.76 0.52 593 0.83 0.56 631 0.89 0.62 698
1600 0.67 0.49 557 0.70 0.54 616 0.75 0.58 654 0.82 0.64 723
1700 0.60 0.52 584 0.63 0.57 646 0.67 0.60 678 0.74 0.66 750
1800 0.51 0.54 610 0.54 0.60 674 0.62 0.62 698 0.69 0.68 772
1900 0.40 0.56 629 0.45 0.62 696 0.54 0.64 720 0.62 0.70 796
2000 0.32 0.58 661 0.33 0.65 731 0.47 0.66 744 0.54 0.73 823
LEGEND
Bhp Brake Horsepower Input to Fan
ESP External Static Pressure (in. wg)
FIOP Factory-Installed Option
Watts Input Watts to Motor
NOTES:
1. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
2. Extensivemotor and electrical testing on these units ensures that the
full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
3. Use of a field-supplied motor may affect wire sizing. Contact your lo-
cal representative for details.
4. Minimum allowable cfm is 300 cfm/ton.
558D048 (4 TON)
Airflow
(Cfm)
Alternate Direct-Drive Motor
External Static Pressure (in. wg)
0.1 0.2 0.3 0.4 0.6 0.7 0.8
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1200 514 0.15 158 590 0.20 210 657 0.25 263 723 0.30 315 828 0.42 441 876 0.49 510 924 0.55 578
1300 545 0.18 189 615 0.23 242 680 0.29 305 744 0.35 368 849 0.47 494 895 0.54 562 940 0.60 630
1400 577 0.21 221 642 0.27 284 704 0.33 347 766 0.39 410 870 0.52 546 915 0.59 620 959 0.66 693
1500 609 0.26 273 670 0.31 326 729 0.38 394 788 0.44 462 892 0.58 609 936 0.65 683 980 0.72 757
1600 642 0.30 315 699 0.36 378 755 0.43 447 811 0.49 515 913 0.64 672 957 0.72 751 1001 0.79 830
1700 675 0.36 378 728 0.42 441 782 0.49 510 836 0.55 578 935 0.71 746 979 0.79 825 1023 0.86 904
1800 709 0.41 431 759 0.48 504 810 0.55 578 860 0.62 651 957 0.78 820 1001 0.86 904 1044 0.94 988
1900 743 0.48 504 790 0.55 578 838 0.62 651 886 0.69 725 980 0.86 904 1023 0.95 993 1066 1.03 1082
2000 778 0.55 578 836 0.62 651 875 0.70 730 913 0.77 809 1004 0.94 988 1046 1.03 1082 1088 1.12 1177
558D048 (4 TON) (cont)
Airflow
(Cfm)
Alternate Direct-Drive Motor
External Static Pressure (in. wg)
1.0 1.1 1.2 1.4 1.6 1.8
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1200 999 0.66 674 1018 0.67 685 1036 0.68 695 1073 0.71 756 1109 0.75 794 1138 0.79 851
1300 1025 0.74 756 1058 0.79 807 1090 0.84 858 1121 0.87 832 1159 0.90 918 1193 0.95 976
1400 1042 0.81 828 1080 0.88 899 1118 0.95 971 1175 1.06 1014 1206 1.09 1042 1244 1.12 1138
1500 1060 0.88 899 1098 0.96 981 1136 1.04 1063 1205 1.19 1138 1258 1.30 1243 1289 1.34 1282
1600 1080 0.95 971 1117 1.04 1058 1153 1.12 1140 1224 1.29 1234 1287 1.45 1387 1337 1.56 1492
1700 1101 1.03 1053 1137 1.12 1139 1172 1.20 1226 1241 1.38 1320 1307 1.56 1492 1366 1.73 1655
1800 1122 1.11 1134 1157 1.20 1226 1192 1.29 1318 1258 1.48 1415 1323 1.67 1597 1385 1.86 1779
1900 1143 1.21 1237 1179 1.30 1328 1214 1.39 1420 1279 1.58 1511 1341 1.78 1702 1402 1.98 1894
2000 1165 1.31 1339 1200 1.40 1431 1235 1.49 1523 1300 1.69 1616 1361 1.90 1817 1419 2.10 2008
LEGEND
Bhp Brake Horsepower Input to Fan
FIOP Factory-Installed Option
Watts Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)
2. indicates field-supplied motor and drive are required.
3.
indicates maximum usable bhp/watts.
4. Maximum usable watts input is 1000 and maximum continuous bhp
is 1.00. Extensive motor and electricaltesting onthese unitsensures
that the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or prematuremotor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
5. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
6. Use of a field-supplied motor may affect wire sizing. Contact your lo-
cal representative for details.
7. Motor drive range: 835 to 1185 rpm. All other rpms require field-
supplied drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
35