Bryant 558D Automobile User Manual


 
AIR DELIVERY 558D036-150 VERTICAL DISCHARGE UNITS (cont)
558D072 (6 TON)
Airflow
(Cfm)
Standard Belt-Drive Motor
External Static Pressure (in. wg)
0.1 0.2 0.4 0.6 0.8
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1800 852 0.55 562 905 0.62 615 1002 0.78 739 1084 0.93 859 1163 1.10 998
1900 894 0.64 630 945 0.72 692 1037 0.88 818 1119 1.04 948 1194 1.21 1089
2000 936 0.74 708 984 0.82 771 1072 0.98 899 1154 1.16 1047 1226 1.33 1190
2100 978 0.85 795 1024 0.93 859 1108 1.10 998 1190 1.29 1156 1259 1.47 1310
2200 1021 0.97 891 1064 1.05 956 1145 1.22 1097 1225 1.43 1275 1294 1.62 1439
2300 1064 1.10 998 1104 1.18 1064 1183 1.36 1216 1260 1.57 1396 1330 1.78 1578
2400 1107 1.24 1114 1145 1.32 1182 1222 1.52 1353 1296 1.73 1534 1365 1.94 1718
2500 1150 1.39 1241 1186 1.48 1318 1262 1.68 1491 1331 1.89 1674 1400 2.12 1875
2600 1193 1.56 1387 1228 1.65 1465 1301 1.86 1648 1367 2.07 1831 1435 2.31 2041
2700 1237 1.74 1543 1269 1.83 1621 1341 2.05 1814 1404 2.26 1997 1471 2.51 2214
2800 1280 1.94 1718 1311 2.03 1796 1381 2.25 1989 1442 2.47 2180 1506 2.72 2394
2900 1324 2.15 1901 1354 2.24 1980 1420 2.47 2180 1481 2.69 2369 1542 2.94 2579
3000 1368 2.37 2093 1396 2.46 2171 1460 2.69 2369 1521 2.93 2571
558D072 (6 TON) (cont)
Airflow
(Cfm)
Standard Belt-Drive Motor
External Static Pressure (in. wg)
1.0 1.2 1.4 1.6
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1800 1235 1.29 1156 1303 1.48 1318 1371 1.69 1499 1433 1.90 1638
1900 1266 1.40 1250 1330 1.59 1413 1396 1.81 1604 1460 2.03 1796
2000 1297 1.53 1361 1362 1.73 1534 1422 1.94 1718 1485 2.16 1910
2100 1327 1.66 1473 1393 1.87 1656 1452 2.08 1840 1510 2.31 2041
2200 1359 1.81 1604 1423 2.02 1779 1483 2.24 1980 1538 2.46 2171
2300 1392 1.97 1744 1454 2.18 1927 1515 2.41 2128 1569 2.64 2326
2400 1426 2.15 1901 1485 2.36 2084 1544 2.59 2283 1601 2.84 2459
2500 1461 2.34 2067 1518 2.55 2249 1575 2.78 2445
2600 1497 2.54 2240 1552 2.76 2428
2700 1532 2.75 2420
2800 ——— —— — —— — —— —
2900 ——— —— — —— — —— —
3000 ——— —— — —— — —— —
LEGEND
Bhp Brake Horsepower Input to Fan
FIOP Factory-Installed Option
Watts Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)
2. indicates field-supplied motor and drive are required.
3.
indicates maximum usable bhp/watts.
4. Maximum usable watts input is 2120 and maximum continuous bhp
is 2.40. Extensive motor and electricaltesting onthese unitsensures
that the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
5. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
6. Use of a field-supplied motor may affect wire sizing. Contact your lo-
cal representative for details.
7. Motor drive range: 1070 to 1460 rpm. All other rpms require field-
supplied drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
29