ELECTRICAL DATA 559F180-300 UNITS (cont)
UNIT
559F
NOMINAL
V-PH-Hz
VOLTAGE
RANGE
COMPRESSOR
OFM IFM
POWER
EXHAUST
ELECTRIC
HEAT*
POWER
SUPPLY
No. 1 No. 2
Min Max RLA LRA RLA LRA Quantity Hp
FLA
(ea)
FLA FLA LRA FLA Nom kW** MCA MOCP††
240
208/230-3-60 187 254 35.6 198 35.6 198 2 1 5.50 25.0/25.0
——
—/— —/— 116/116 150/150
72/ 82 26/34 121/134 150/150
117/135 42/56 178/166 200/175
156/180 56/75 187/211 200/225
4.6 18.8
—/— —/— 121/121 150/150
72/ 82 26/34 127/140 150/150
117/135 42/56 183/172 200/175
156/180 56/75 193/217 200/225
460-3-60 414 508 17.8 99 17.8 99 2 1 2.80 13.0
——
59 70
39 32 65 70
66 55 82 90
96 80 112 125
2.3 6.0
61 70
39 32 68 70
66 55 85 90
96 80 115 125
575-3-60 518 632 14.3 79 14.3 79 2 1 3.40 10.0
49 60
2.1 4.8 51 60
300
208/230-3-60 187 254 43.6 228 43.6 228 2 1 5.50 28.0/28.0
——
—/— —/— 137/137 175/175
72/ 82 26/34 137/138 175/175
117/135 42/56 181/170 200/175
156/180 56/75 191/215 200/225
4.6 18.8
—/— —/— 142/142 175/175
72/82 26/34 142/143 175/175
117/135 42/56 187/176 200/200
156/180 56/75 197/221 200/225
460-3-60 414 508 22.1 114 22.1 114 2 1 2.80 14.6
——
70 90
39 32 70 90
66 55 84 90
96 80 114 125
2.3 6.0
72 90
39 32 72 90
66 55 87 90
96 80 117 125
575-3-60 518 632 17.9 91 17.9 91 2 1 3.40 13.0
60 70
2.1 4.8 62 80
LEGEND AND NOTES FOR ELECTRICAL DATA TABLES ON PAGES 49-54
LEGEND
FLA Full LoadAmps
HACR Heating, Air Conditioning and Refrigeration
IFM Indoor (Evaporator) Fan Motor
LRA Locked Rotor Amps
MCA Minimum CircuitAmps
MOCP Maximum Overcurrent Protection
NEC National Electrical Code
OFM Outdoor (Condenser) Fan Motor
RLA Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and
575 v. Heaters are rated at 240 v, 480 v, or 575 v. If power distribution voltage
to unit varies from rated heater voltage, heater kW will vary accordingly. To de-
termine heater capacity at actual unit voltage, multiply 240 v, 480 v, or 575 v
capacity by multipliers found in Electric Heat Multiplication Factors table on
page 48.
†Used to determine minimum disconnect size per NEC.
**Heaters are field installed only.
††Fuse or HACR circuit breaker.
Fusing in single point box provides the required branch circuit protection.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NECArticles 430 and 440), the overcurrent protective de-
vice for the unit shall be fuse or HACR breaker. The Canadian units may be
fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2%.
Use the following formula to determine the percent of voltage
imbalance.
max voltage deviation from average voltage
% Voltage Imbalance = 100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.
3. MCAcalculation for units withelectric heaters over 50 kW = (1.25 x IFM amps)
+ (1.00 x heater FLA).
036-150 Only 036-072 Only
090-150 Only 180-300 Only 180-300 Only