Bryant 558D Automobile User Manual


 
APPLICATION DATA (cont)
EVAPORATOR-FAN MOTOR PERFORMANCE
UNIT
EVAPORATOR-FAN
MOTOR
UNIT
VOLTAGE
MAXIMUM
ACCEPTABLE
CONTINUOUS
BHP*
MAXIMUM
ACCEPTABLE
OPERATING
WATTS
MAXIMUM
AMP DRAW
558D036
Standard
208/230
0.34 440
2.9
460 1.4
575 1.4
Alternate
208/230
1.00 1000
5.1
460 2.3
575 2.3
558D048
Standard
208/230
0.75 850
3.7
460 1.9
575 1.9
Alternate
208/230
1.00 1000
5.1
460 2.3
575 2.3
558D060
Standard
208/230
1.20 1340
6.2
460 3.4
575 3.4
Alternate
208/230
1.80 1921
6.1/9.2†
460 2.7
575 2.7
558D072 Standard
208/230
2.40 2120
6.1
460 2.7
575 2.7
558D090 Standard
208/230
2.40 2120
6.1
460 2.7
575 2.7
558D102 Standard
208/230
2.40 2120
6.1
460 2.7
575 2.7
558D120
Standard
208/230
2.40 2120
6.1
460 2.7
575 2.7
Alternate
208/230
2.90 2615
7.9
460 3.6
575 3.6
558D150
Standard
208/230
4.20 3775
12.6
460 5.7
575 5.7
Alternate
208/230
5.25 4400
15.0
460 7.4
575 7.4
559F180 Standard
208/230
4.25 3775
10.5
460 4.8
575 3.45 3065 3.9
559F216 Standard
208/230
5.90 5180
15.8
460 7.9
575 6.0
559F240 Standard
208/230 8.70 7915 25.0
460 9.50 8640 13.0
575 8.70 7915 10.0
559F300 Standard
208/230 10.26 9510 28.0
460 11.80 11,000 14.6
575 10.26 9510 13.0
LEGEND
BHP Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower range of the motors can be
utilized with confidence. Using your fan motors up to the horsepower ratings shown in this table will not result in
nuisance tripping or premature motor failure. Unit warranty will not be affected.
†Single phase/3 phase.
62