Series 220/221 Instruction Manual Chapter 4 HART Communications
Fast Key Sequence
Use password 16363.
Sequence Description Access Notes
1,1,1 Snsr View Primary variable value
1,1,2 AI % Rnge View Analog output % range
1,1,3 AO1 View Analog output, mA
1,2,1 Test Device N/A Not used
1,2,2,1 4 mA View Loop test, fix analog output at 4 mA
1,2,2,2 20 mA View Loop test, fix analog output at 20 mA
1,2,2,3 Other Edit Loop test, fix analog output at mA value entered
1,2,2,4 End Exit loop test
1,2,3,1,1 4 mA N/A Not used, apply values
1,2,3,1,2 20 mA N/A Not used, apply values
1,2,3,1,3 Exit Exit apply values
1,2,3,2,1 PV LRV Edit Primary variable lower range value
1,2,3,2,2 PV URV Edit Primary variable upper range value
1,2,3,2,3 PV USL View Primary variable upper sensor limit
1,2,3,2,4 PV LSL View Primary variable lower sensor limit
1,2,4 D/A Trim Edit Calibrate electronics 4mA and 20mAvalues
1,3,1 Tag Edit Tag
1,3,2 PV unit Edit Primary variable units
1,3,3,1 PV LRV Edit Primary variable lower range value
1,3,3,2 PV URV Edit Primary variable upper range value
1,3,3,3 PV LSL View Primary variable upper sensor limit
1,3,3,4 PV USL View Primary variable lower sensor limit
1,3,4,1 Distributor N/A Not used
1,3,4,2 Model N/A Not used
1,3,4,3 Dev id View Device identification
1,3,4,4 Tag Edit Tag
1,3,4,5 Date Edit Date
1,3,4,6 Write Protect View Write protect
1,3,4,7 Descriptor Edit Vortex flowmeter
1,3,4,8 Message Edit 32 character alphanumeric message
1,3,4,9 PV snsr s/n View Primary variable sensor serial number
1,3,4,menu Final assy # Edit Final assembly number
1,3,4,menu,1 Universal Rev View Universal revision
1,3,4,menu,2 Fld dev Rev View Field device revision
1,3,4,menu,3 Software Rev View Software revision
1,3,5 PV Xfer fnctn View Linear
1,3,6 PV Damp Edit Primary variable damping (time constant) in seconds
1,4,1,1 PV View Primary variable value
1,4,1,2 PV Sensor Unit Edit Primary variable units
1,4,1,3 Sensor Information View PV LSL, PV USL, PV Min span
1,4,2,1 Snsr Damp Edit Primary variable damping (time constant) in seconds
1,4,2,2,1 PV LRV Edit Primary variable low range value
1,4,2,2,2 PV URV Edit Primary variable upper range value
1,4,2,3,1 PV LRV Edit Primary variable low range value
1,4,2,3,2 PV URV Edit Primary variable upper range value
1,4,2,4 Xfer Fnctn View Linear
1,4,2,5 AI % rnge View Analog output % range
1,4,3,1,1 AO1 View Analog output, mA
1,4,3,1,2 AO alarm typ N/A Not used