RVS-DX, Digital Soft Starter Instruction Manual—4/01/04
A-4
Control:
Displays LCD in 4 (field selectable) languages and 4 LEDs
Keypad 6 keys for easy setting
Aux. Contact–immediate or end of
accel
1 N.O., 8A, 250 VAC, 2000 VA
Fault Contact 1 N.O., 8A, 250 VAC, 2000 VA
Temperatures:
Operating Temperature -10°C to +40°C
Storage Temperature -20°C to +70°C
Standards:
Dielectric Test 2500 VAC
Degree of Protection IP20 for frame size A1
IP00 for frame size A2-A5
Pollution Degree 3
EMC
Emissions
Immunity
Safety
EN 55011 CISPR 11 Class A
EN 55082-2 ESD 8KV air, IEC 801-2
Fast transients 2KV, IEC 801-4
EN 600947-1 Related to safety requirements.
UL508C
UL508c listed on units 8-170 Amps
Normal Service Conditions
Altitude Up to 1000m. For equipment to be used at high altitudes consult Factory.
Humidity 95% at 50°C or 98% at 45°C.
Starter Consumption Ratings:
Size A1 & A2 Total starter consumption: 185VA
Size A3-A5 Total starter consumption: 215VA