Magnetek 188-10130 Remote Starter User Manual


 
RVS-DX, Digital Soft Starter Instruction Manual—4/01/04
8-4
WRONG PARAMETERS Parameters were not transferred from RAM to EEPROM. This may happen after
replacing the EEPROM with a new version program. Press “Reset” key, then “Mode”
and down arrow keys simultaneously and save new default parameters by pressing
“Store” and “Mode” keys simultaneously. (If “Fault” LED is illuminated, press
“Reset” key after storing parameters.)
NOTE: When operating in generator mode, shorted SCR and wrong connection faults are not active.
Fault Description