RVS-DX, Digital Soft Starter Instruction Manual—4/01/04
6-3
Mode
Mode
Mode
Mode Mode
Upon Initiation
Parameter Display
Page 1
Page 2 Page 3 Page 4
Select
Select Select Select
Select
% Of Motor FLA
Main Parameters
Start Parameters
Stop Parameters Dual Adj. Parameters
To Review All
Parameters
Press
Keys To Change Parameter Value
Option Card Not
Installed
BACK TO TOP
Starter FLC
105 Amp
Motor FLA
105 Amp
Undercurr. Trip
0% Of FLA
Undervolt. Trip
75%
O/C Shear Pin
850% Of FLA
Overload Trip
115% of FLA
Overload Delay
4 Sec.–at 5 FLA
Undervolt.
Delay 5 Sec.
Under Curr.
Delay 10 Sec.
Overvolt. Trip
120%
Overvolt. Delay
2 Sec.
Store Enable
Main Parameters
BACK TO TOP
Soft Start Curve
0 (Standard)
Start Tacho Gain
0 (Min. Gain)
Pulse Time
0 Sec.
Initial Voltage
30%
Current Limit
400% of FLA
ACC. Time
10 Sec.
Max. Start Time
30 Sec.
Number of Starts
10
Starts Period
30 Min.
Start Inhibit
15 Min.
Store Enable
Start Parameters
Soft Stop Curve 0
(Standard)
Stop Tacho Gain 0
(Min. Gain)
Final Torque
0 (Min)
Dec. Time
0 Sec.
Store Enable
Stop Parameters
DA: (Generator)
Parameters
DA: Int. Volt
30%
DA: Cur. Limit
400% of FLA
DA: Acc. Time
100 Sec.
DA: Dec. Time
0 Sec.
DA: Motor FLA
105 Amp
Store Enable D.
Adj. Parameters
BACK TO TOP
BACK TO TOP
BACK TO TOP
When DIP SW#1.2 is set ON
When Prog. Input C! is set to
Generator Start/Stop
Initial Current
100%
DA: Int. Current
100%
Note: Available after
initial voltage setting
is above maximum level.
Connection Type
Line
Rated Line Volt.
460 Volt
O/C Delay
0.5 Sec.
Display Mode
Minimized
Parameters Lock
Not Locked