RVS-DX, Digital Soft Starter Instruction Manual—04/01/04
4-6
Extended Parameter Setting
The RVS-DX incorporates a parameter, “WIDER SETTINGS”, in the special Features Parameters.
If the RVS-DX is significantly larger than your motor, you can enable the “wider settings” to extend
parameter settings of the following:
Extended Parameter Settings
Parameter Original Setting Range Extended Setting Range
Initial Voltage 10-50% 10-80%
Current Limit 100-400% 100-500%
Acceleration Time 1-30 seconds 1-90 seconds
Deceleration Time 0-30 seconds 0-90 seconds
Max. Start Time 1-30 seconds 1-250 seconds