FAULT PARAMETERS (display mode set to maximized to access)
Parameter Description/Function Default Value Range Access
PHASE SEQ. Y/N
INSULATION ALARM
INSULATION TRIP
AUTO RESET
THERMISTOR TYPE
THERMISTOR TRIP
UNDER CUR. RESET
STORE ENABLE
FAULT PARAMETERS
Phase sequence trip setting
Insulation alarm setting
Insulation trip setting
Auto reset 'on/off' setting
Thermistor type setting
Thermistor trip setting
Under current auto reset time setting
Press 'Store' to save changes made to any of the
Fault Parameters
NO
OFF
OFF
NO
PTC
OFF
OFF
Yes=on; No=off
off; 0.2-5 Mohm
off; 0.2-5 Mohm
Yes=on; No=off
PTC, NTC
off; 0.1-10.0 Kohm
10-120 min.; off
maximized
maximized
maximized
maximized
maximized
maximized
I/O PROGRAMMING PARAMETERS (display mode set to maximized to access)
Parameter Description/Function Default Value Range Access
PROG.INPUT C1
FAULT RELAY TYPE
PROG. AUX. RELAY
RELAY ON DELAY
RELAY OFF DELAY
ANALOG OUTPUT
STORE ENABLE
I/O PROG. PARAM
Sets terminal C1 to: Dual adjust, generator mode,
slow speed/reverse, external fault, remote reset.
Fault
Fault-fail safe
Immediate or End of Accel
Time Delay before relays turns on
Time Delay before relay turns off
Normal=output increases with increasing current
Inverted=output increases with decreasing current
Press 'Store' to save changes made to any of the I/
O Programming Parameters
Remote Reset
Fault
Immediate
0
0
Normal
Dual Adjustment,
Generator mode, slow
speed/rev., external
fault, reset
Fault, Fault-Fail Safe
Immediate, End of
Accel.
0-60 seconds
0-60 seconds
Normal, Inverted
maximized
maximized
maximized
maximized
maximized
maximized
COMMUNICATION PARAMETERS (display mode set to maximized to access)
Parameter Description/Function Default Value Range Access
COMM. PROTOCOL
DRIVE NUMBER
BAUD RATE
PARITY CHECK
SERIAL LINK NO.
STORE ENABLE
COMM.PARAMETERS
Serial Communicaitons protocol selection
Drive number setting
Baud rate setting
Parity Check setting
Serial link number
Press 'Store' to save changes made to any of the
Communication Parameters
Modbus
0
9600
Even
248 (off)
Modbus, Profibus
0-999
1200, 2400, 4800, 9600
Even, Odd, NO
1-248
maximized
maximized
maximized
maximized
maximized