Toshiba ME00070B Remote Starter User Manual


 
PROGRAMMING
18 ME00070B TMS7 SERIES
7.2 Function List
No. Function
Primary Motor Settings
Default
Setting
1 Motor full load current -
2 Current limit 350
3 Minimum current 350
4 Start ramp time 1
5 Stop ramp time 0
6 Motor trip class 10
7 Current imbalance sensitivity 5
8 Undercurrent protection 20
9 Stall protection 400
Start/Stop Formats
10 Soft stop mode 0
Starter Functionality
20 Local/Remote operation 0
21 Relay output A functionality 11
22 Relay output B functionality 10
23 Relay output C functionality 0
Protection Settings
30 Phase rotation 0
31 Restart delay 15
32 Current imbalance 0
Set Points
40 Low current alarm 50
41 High current alarm 105
42 Motor temperature alarm 80
43 Field calibration 100
Analogue Output (Motor Current - % FLC)
50 4-20mA output range - max 100
51 4-20mA output range - min 0
Serial Communications
60 RS485 timeout 0
61 RS485 baud rate 4
62 RS485 satellite address 20
Auto Reset
70 Auto-reset - configuration 0
71 Auto-reset - number of resets 1
72 Auto-reset - group A & B delay 5
73 Auto-reset - group C delay 5
Secondary Motor Settings
80 Motor full load current -
81 Current limit 350
82 Minimum current 350
83 Start ramp time 1
84 Stop ramp time 0
85 Motor trip class 10
86 Current imbalance sensitivity 5
87 Undercurrent protection 20
88 Stall protection 400
Protection Delays
90 Current imbalance trip delay 3
Read Only Data
100 Model Number -
101 Fault History -
Restricted Functions
110 Access code 0
111 Update access code 0
112 Function lock 0
113 Restore function settings 0
7.3 Function Descriptions
1. Motor Full Load Current
Range: Model Dependant (Amps)
Default Setting: Model Dependant (Amps)
Description: Sets the TMS7 for the connected motor’s full load
current.
Adjustment: Set to the Full Load Current (amps) rating shown
on the motor nameplate.
2. Current Limit
Range: 100 550 % FLC
Default Setting: 350% FLC
Description: Sets the current limit for the Constant Current start
mode.
700%
500%
300%
100%
50% 100%
ROTOR SPEED
(% Full Speed)
eg. Function 2. Current Limit = 350% x FLC
Adjustment: The required setting for the Current Limit function
is installation dependant and should be set such that:
The motor is supplied with sufficient start current to enable
it to produce torque adequate to easily accelerate the
connected load.
Desired starting performance is obtained.
TMS7 ratings are not exceeded.
3. Minimum Current
Range: 100 550 % FLC
Default Setting: 350% FLC
Description: Sets the minimum current level for the Ramp Start
mode.
700%
500%
300%
100%
50% 100%
ROTOR SPEED
(% Full Speed)
Function. 2 Current Limit = 350% x FLC
Function. 3 Minimum Current = 200% x FLC
Function. 4 Start Ramp Time = 10 secs