6) Pump-Out Cycle – The 1st pump out occurs after the 11th freeze cycle and every
10th cycle thereafter. LEDs 1, 3,  are on. The compressor and fan motors remain
energized. The drain water valve, hot gas valves and X1 relay energize, the liquid line
valves de-energize. The pump motor stops for  seconds then restarts for 10 seconds
(pump out frequency can be adjusted on S4 dip switches 5 and 6). This pump out
removes contaminants from the water reservoir through the drain water valve and
allows for a power ush of the oat switch. Diagnosis: If the pump motor does not
come on, check the circuit and capacitor. If water does not pump out, remove the drain
water valve housing and check/clean the valve assembly, check for voltage on the
drain valve coil with LED 3 on, make sure that the drain line is not clogged.
7) Normal Harvest Cycle – Same as the initial harvest cycle. Return to step 4.
Note: Unit continues to cycle until bin control is satised or power is switched off. The
unit always restarts at the 1 minute ll cycle.