SETTINGS
OPTION SETTINGS
NOTE: The list of available options and the settings associated with them will vary with each controller. Listed below
are the most common user de ned settings that may appear.
1
AUDIBLE
Use arrows to enable or disable the audible alarm for selected option. Press to con rm.
1
COMMON ALARM
Use arrows to enable or disable the common alarm output (ALR relay) for selected option.
Press to con rm.
1
PUMP ROOM
Use arrows to select the alarm output relay for selected option (Disabled, PTR (Pump Room Trouble), ETR (En-
gine Trouble), Both PTR and ETR). Press to con rm.
EVENT LOG
The Event Log is a record of events (pressure recording, alarms, starts, etc...) that are stored in the memory of the
Mark IIXG. The last 3000 events are kept in this memory. The events are stored in the order that they occur, with the
most recent being “ rst” (the last event that occurred will be event #1). The following keys are used to browse through
the event log:
Move forward through the events one at a time (1 - 2 - 3....etc)
Move backward through the events one at a time (55 - 54 - 53....etc)
Move forward through the events ten at a time (60 - 70 - 80....etc)
Move backward through the events ten at a time (91 - 81 - 71....etc)
Pressing and holding of the arrow keys will allow the scrolling to move faster.
DATA HISTORY
The Data History is a record of important data and events that are kept throughout the life of the controller.
Use arrows to scroll through the information stored in the Data History log. The available information is:
Numbers of calls to start • Number of actual starts • Pump total run time • Pump last run time • Total controller
power on time • Last pump start time/date • Minimum system pressure • Maximum system pressure • Last high
temp. alarm time/date • Last low oil pressure time/date • Last low fuel level time/date • Last charger failure time/
date • Last battery trouble time/date • Last engine overspeed time/date • Battery 1 & 2 voltage min/current/max •
Battery 1 & 2 amps min/current/max
USB
1
SAVE TO USB
Use arrows to enable or disable the Save to USB function. Press to con rm.
The following is saved to the USB ash drive: Event Log, Data History, Controller Information and all user de ned
settings (pressure settings, timer settings, alarm settings....etc.). The saved le is a text le named the same as the
controller serial number (87654321.txt) and can be viewed using most word processing software.
14
SETTINGS
FEATURE SETTINGS
HIGH RESERVOIR
1
AUDIBLE
Use arrows to enable or disable the audible alarm for High Reservoir Level. Press to con rm.
1
COMMON ALARM
Use arrows to enable or disable the common alarm output (ALR relay) for High Reservoir Level.
Press to con rm.
1
PUMP ROOM
Use arrows to select the alarm output relay for High Reservoir Level (Disabled, PTR (Pump Room Trouble), ETR
(Engine Trouble), Both PTR and ETR). Press to con rm.