Use arrows to set maximum voltage point for Battery Trouble alarm. Press to confi rm.
SETTINGS
ALARM LIMITS
1
MAX
Use arrows to set minimum voltage point for AC Voltage Low alarm. Press to confi rm.
SETTINGS
ALARM LIMITS
1
V MIN
Use arrows to set maximum voltage point for AC Voltage High alarm. Press to confi rm.
SETTINGS
ALARM LIMITS
1
V MAX
ENABLED
Use arrows to enable or disable the AC Voltage High alarm. Press to confi rm.
1
ENABLED
Use arrows to enable or disable the AC Voltage Low alarm. Press to confi rm.
1
SETTINGS
ALARM LIMITS
1
COIL CHECK
Use arrows to set monitoring of the engine starting solenoid coils (1-, -2, 1&2, OFF). Press to confi rm.
Settings - Feature Settings
SETTINGS
FEATURE SETTINGS
1
AC POWER LOSS START
ENABLED
Use arrows to enable or disable the AC Voltage Loss Start feature. Press to confi rm.
1
DELAY
Use arrows to set the time delay between loss of AC voltage and engine starting (0-60 sec.).
Press to confi rm.
SETTINGS
FEATURE SETTINGS
1
INTERLOCK ALARM
Use arrows enable or disable the alarm for Interlock On. Press to confi rm.
SETTINGS
FEATURE SETTINGS
1
LOW PRESSURE AUD
Use arrows enable or disable the audible alarm for Low System Pressure. Press to confi rm.
11
Use arrows to enable or disable the alarm for Low Suction Pressure. Press to confi rm.
SETTINGS
FEATURE SETTINGS
LOW SUCTION
1
AUDIBLE
Use arrows to enable or disable the audible alarm for Low Suction Pressure. Press to confi rm.
1
COMMON ALARM
Use arrows to enable or disable the common alarm output (ALR relay) for Low Suction Pressure.
Press to confi rm.
1
PUMP ROOM
Use arrows to select the alarm output relay for Low Suction Pressure (Disabled, PTR (Pump Room Trouble), ETR
(Engine Trouble), Both PTR and ETR). Press to confi rm.
1
ENABLE
SETTINGS
FEATURE SETTINGS
MAIN SWITCH MIS-SET
1
Use arrows to choose how the Main Switch Mis-Set alarm relay operates. “Pick Up” means the relay will ener-
gize when the switch is not in auto. “Drop Out” means the relay we de-energize when the switch is not in auto.
Press to confi rm.