SETTINGS
FEATURE SETTINGS
RELIEF VALVE OPEN
1
AUDIBLE
Use arrows to enable or disable the audible alarm for Relief Valve Open. Press to con rm.
1
COMMON ALARM
Use arrows to enable or disable the common alarm output (ALR relay) for Relief Valve Open.
Press to con rm.
1
PUMP ROOM
Use arrows to select the alarm output relay for Relief Valve Open (Disabled, PTR (Pump Room Trouble), ETR
(Engine Trouble), Both PTR and ETR). Press to con rm.
1
AT
Use arrows to choose the time of day that the Weekly Test is performed. Press to con rm.
1
FOR
Use arrows to choose the duration (engine run time) of the Weekly Test. Press to con rm.
1
NOW IN WEEK
Use arrows to choose current time frame in reference to the Weekly Test schedule. Press to con rm.
(Example: If test is programmed for every 2 weeks on Sunday and today were Friday then - If testing is desired to start
this week, then every other week thereafter, we would now be in week 2 of 2 - If testing is desired to start on the fol-
lowing Sunday, not the coming Sunday, then we would now be in week 1 of 2).
SETTINGS
FEATURE SETTINGS
LOW PUMP ROOM TEMP
1
AUDIBLE
Use arrows to enable or disable the audible alarm for Low Pump Room Temperature. Press to con rm.
1
COMMON ALARM
Use arrows to enable or disable the common alarm output (ALR relay) for Low Pump Room Temperature.
Press to con rm.
1
PUMP ROOM
Use arrows to select the alarm output relay for Low Pump Room Temperature (Disabled, PTR (Pump Room
Trouble), ETR (Engine Trouble), Both PTR and ETR). Press to con rm.
SETTINGS
FEATURE SETTINGS
LOW RESERVOIR
1
AUDIBLE
Use arrows to enable or disable the audible alarm for Low Reservoir Level. Press to con rm.
1
COMMON ALARM
Use arrows to enable or disable the common alarm output (ALR relay) for Low Reservoir Level.
Press to con rm.
1
PUMP ROOM
Use arrows to select the alarm output relay for Low Reservoir Level (Disabled, PTR (Pump Room Trouble), ETR
(Engine Trouble), Both PTR and ETR). Press to con rm.
SETTINGS
FEATURE SETTINGS
HIGH FUEL LEVEL
1
AUDIBLE
Use arrows to enable or disable the audible alarm for High Fuel Level. Press to con rm.
1
COMMON ALARM
Use arrows to enable or disable the common alarm output (ALR relay) for High Fuel Level.
Press to con rm.
1
PUMP ROOM
Use arrows to select the alarm output relay for High Fuel Level (Disabled, PTR (Pump Room Trouble), ETR (En-
gine Trouble), Both PTR and ETR). Press to con rm.