TD Series Digital Solid State Soft Starter 48 - 1250A
5.5.9 System Settings
F060 = Parameter Lock / User Password
Factory Setting = 0 (disabled)
Range = 0 - 999
Provides users with the ability to prevent unauthorized operators from
making changes to the programmed functions. If you do not need to
take advantage of this feature, do not enter anything into this
function. The factory default is disabled, and no Password is necessary
to make changes to the program.
See Appendix 3 at the end of this manual for detailed instructions on
using and altering the Parameter Lock / User Password feature.
F061 = Emergency Clear / Reset
Factory Setting = 0 (disabled)
Range = 0 - 2
This Function serves two purposes. It can clear the memory values
used for lockouts and overload protection, and it can reset all functions
to the factory default settings.
When F061 = 0, the feature is disabled. This is a “One-Shot” feature,
so when another value is entered as shown below, this function
automatically returns to the default state.
When F061 = 1, the values stored in the Thermal Register and all of the
Lockout Timers will be cleared. This will allow an emergency restart
without having to wait for proper cool down time or lockout timers to
expire.
Clearing the Thermal Register to allow restarting without
proper cool-down time after an Overload Trip will risk motor
damage and fire. Use only where emergency restart is
necessary without regard to these potential hazards.
When F061 = 2, the values of all functions will be reset to the factory
default settings. Use this feature when settings conflict or have been
tampered with. This is also useful when you lose track of experimental
settings and wish to start over.
Note: This will not reset F060 = Parameter Lock / User Password.
F062 = Reserved
F063 = Reserved for Factory Use
F064 = Reserved for Factory Use
5.5.9.a Real Time Clock Settings
Functions F065 through F070 set the system real time clock. The time clock is
primarily used in date/time stamping Fault History. Time clock automatically
adjusts for leap years. Time clock does not automatically adjust for daylight
savings time.
F065 = Year
Factory Setting = Year of manufacture
Range = 2000 to 2047
F066 = Month
Factory Setting = Month of manufacture
Range = 1 - 12
WARNING