- 28 -
TD Series Digital Solid State Soft Starter 48 - 1250A
F043 = Time Between Starts Lockout
Factory Setting = 0 (Disabled)
Range = 0 - 1
If F043= 1, the motor cannot be started within the time specified in
F044. Time between starts is calculated from the time of the first start
command to the next regardless of run time. (Used in conjunction with
F041).
Time Between Starts Lockout
F044 = Minimum Time Between Starts
Factory Setting = 15 minutes
Range = 1 - 60 minutes
If F043 = 1 and F044 = 15, motor will not start within 15 minutes of first
start.
F045 = Coast Down Timer Value
Factory Setting = Not Applicable
Range = 1 - 3600 Seconds
Display for information only; value cannot be altered by the user.
Readout only for user’s viewing of remaining time value of the Coast
Down Lockout Timer.
F046 = Starts per Hour Timer Value
Factory Setting = Not Applicable
Range = 1 - 3600 Seconds
Display for information only; value cannot be altered by the user.
Readout only for user’s viewing of remaining time value of Starts-per-
Hour Lockout Timer.
F047 = Starts per Hour
Factory Setting = Not Applicable
Range = 1 - 10 Starts
Display for information only; value cannot be altered by the user.
Readout only for user’s viewing of the accumulated Starts-per-Hour
value used in the Lockout function.
F048 = Time Value Between Starts
Factory Setting = Not Applicable
Range = 1 - 3600 Seconds
Display for information only; value cannot be altered by the user.
Readout only for user’s viewing of remaining time value of Minimum
Time Between Starts Timer.