Toshiba 48-1250 A Remote Starter User Manual


 
TD - Series
- 31 -
TD Series Digital Solid State Soft Starter 48 - 1250A
F067 = Day
Factory Setting = Day of manufacture
Range = 1 - 31
F068 = Hour
Factory Setting = Actual (EST)
Range = 0 - 23 (12:00 midnight is hour 0)
F069 = Minute
Factory Setting = Actual (EST)
Range = 0 - 59
F070 = Second
Factory Setting = Actual (EST)
Range = 0 - 59
F071 = Reserved for Factory Use
F072 -F074 = Reserved
5.5.10 Fault History and Run Time
The fault history will store the three last fault conditions plus the date and time
that each fault occurred.
F075 = Fault History # 1, Latest Fault
Factory Setting = 0000
Range = NA
Displays 2-digit fault number. See Chapter 7.
F076 = Time Stamp, Fault # 1
Factory Setting = 00.00
Range = HH.MM where HH = 00 - 23 and MM = 00 - 59
Displays time fault in F075 was detected.
F077 = Date Stamp, Fault # 1
Factory Setting = 01.01
Range = MM.DD where MM = 01 - 12 and DD = 01 - 31
Displays date time fault in F075 was detected.
F078 = Fault History # 2, Previous Fault
Factory Setting = 0000
Range = NA
Displays 2-digit fault number. See Chapter 7.
F079 = Time Stamp, Fault # 2
Factory Setting = 00.00
Range = HH.MM where HH = 00 - 23 and MM = 00 - 59
Displays time fault in F078 was detected.
F080 = Date Stamp, Fault # 2
Factory Setting = 01.01
Range = MM.DD where MM = 01 - 12 and DD = 01 - 31
Displays date time fault in F078 was detected.
F081 = Fault History # 3, Oldest Fault
Factory Setting = 0000
Range = NA
Displays 2-digit fault number. See Chapter 7.
F082 = Time Stamp, Fault # 3
Factory Setting = 00.00
Range = HH.MM where HH = 00 - 23 and MM = 00 - 59
Displays time fault in F081 was detected.