TD Series Digital Solid State Soft Starter 48 - 1250A
6.1 Quick Start
Your new TD Series Soft Starter is factory preset for a wide variety of applications
and often can be used with minimal adjustment.
6.1.1. Three Step Process
1. Connect L1, L2, and L3 to power lines and T1, T2, and T3 to motor.
2. Connect control wires and control power.
3. Program motor FLA (F001).
6.1.2 TD Start-up Parameters and Factory Defaults
Try the initial presets first and then adjust or enable the more advanced features
to meet your specific starting needs.
Chapter 6 - Start-up
TB1 Two-Wire Connection
(alternate connection)
TB1 Three-Wire Connection
(See page 20 for more information)
Function
Number
Function
Name
Factory
Setting
Description
F001 Motor Nameplate FLA 0
Starter disabled
Unit must be set to actual motor
FLA
F002 Motor Service Factor 1.0
Motor Service Factor
from motor nameplate
F003
Overload Protection
During Start
10
NEMA Overload Class
(Class 10)
F004
Overload Protection
During Run
10
NEMA Overload Class
(Class 10)
F005 Overload Reset 0 Manual Reset
F010 Ramp Profile 1
Ramp 1 is voltage ramp
with current limit;
Ramp 2 is voltage ramp
with current limit
F011 Initial Torque 60 60 Percent
F013 Ramp Time 10
10 second time duration
for Ramp 1
F014
Current Limit 350
Maximum current limit of Ramp
1 as a percentage (350%).
F015-F018
Ramp 2 60,200,10,350
Inactive unless TB4 control
circuit is wired
F019-F021 Jog 50,10,150
Inactive unless TB4 control
circuit is wired
F022-F049
All other protection
and control features
See Note Disabled
F050
Aux. Relay #1
(TB2, terminals 1 - 3)
1 Run / Stop
F051
Aux. Relay #2
(TB2, terminals 4 - 6)
2 At Speed / Stop
F052
Aux. Relay #3
(TB2, terminals 7 - 9)
14 Any Fault
F060
Parameter Lock /
User Password
0 User password disabled
F066-F070
All Time Values 0 Eastern Standard Time
F075-F083 Fault Histories Clear Entered upon occurrence
TB2
AUX 1
Fn F050
AUX 2
Fn F051
240 VAC
AUX 3
Fn F052
Optical
Triac Driver
MOTOR FLA (F001)
must be programmed
for unit to operate.