Mitsubishi Electronics QJ72LP25-25 Automobile Electronics User Manual


 
52
(4) Intelligent function module parameter
Parameters for intelligent function modules mounted on the MELSECNET/H (MELSECNET/10 mode) remote I/O
station can be set.
However, the auto refresh parameter cannot be set.
If set, SP. PARA ERROR (error code: 3301) occurs.
Read/write data from/to the buffer memory using the ZNFR/ZNTO instructions.
Remark
The availability and the number of initial setting items differ depending on the intelligent function module used.
( User's manual for the intelligent function module used)
If the items are set exceeding the limit, the MELSECNET/H remote I/O module detects SP.PARA ERROR (error code:
3301).
Item Description
Initial setting
Set the parameter for the intelligent function module.
Up to 512 initial setting items can be set.
The number of setting items differs depending on the intelligent function module used.
For the Q64AD (GX Configurator-AD)
Ex.
The number of initial setting items for
the Q64AD is two. Add this number to
the number of setting items for other
intelligent function modules.