C. Route the Sensor Harness to the Sensors.
Connect the ring terminals of the Sensor
Harness to the Sensors. Refer to Section 12 of
the Retrofit Application Data, supplied with the
Retrofit Kit, for detailed wiring specifications.
Depending on the Sensors supplied with the
Retrofit Kit, the following Ratings apply.
Sensor Style No. Terminal Com. Amps
8184A39H01 X1 - X4 = 600 A
X2 - X4 = 400 A
X1 - X2 = 200 A
Fig. 48 Sensors Installed on the Breaker
Table 3 Sensor Taps Rating
Fig. 49 Sensors Harness Connected to the