A SERVICE OF

logo

Effective 4/00
IL 33-FX6-1
Page 18
I. Attach the Glass Poly Insulation Plate to the
top of the CPT, as shown, using the (2) .138-20
× .375" thread cutting screws, (2) lock washers,
and (2) flat washers supplied.
K. Align the Trip Unit Assembly with the existing
holes in the bottom Breaker Frame. Secure the
Trip Unit Assembly to the Breaker, as shown,
using the (4) .250-20 × .750" screws, (4) lock
washers, (8) flat washers, and (4) nuts supplied.
Note that the bolts are inserted from the bot-
tom of the Breaker.
For All Breakers.
J. Align the Trip Unit Assembly with the bottom of
the Breaker Frame. Note that the Aux. CT
Module Mounting Brackets are “notched” to
form a natural guide for the Trip Unit Assembly.
Fig. 36 Insulation Plate Mounted to the CPT
Fig. 37 Alignment of the Trip Unit Assembly and
the Bottom Breaker Frame
L. Install the Digitrip Retrofit Label on the top
Breaker Shelf.
Fig. 38 Trip Unit Assembly Installed in the
Breaker
Fig. 39 Digitrip Retrofit Label Installed on the
Breaker