Effective 4/00
Page 13
IL 33-FX6-1
B. For Kits Supplied with a PT Module Only: Align
the Glass Poly Insulation Barrier and the PT
Module with the holes in the top of the Aux. CT
Module, as shown. Secure the PT Module and
Insulation Plate to the Aux. CT Module using
the (2) .138-32 × .375" thread cutting screws,
(2) flat washers, and (2) lock washers supplied.
D. For Kits Supplied with a PT Module Only:
Route the PT Wires under the PT Module and
Aux. CT Module to the rear of the Assembly.
E. Align the Trip Unit with the holes in the Trip Unit
Mounting Platform, as shown. Secure the Trip
Unit to the Trip Unit Mounting Platform using
the (2) brass spacers, (2) .190-32 × 4.00"
screws, (4) flat washers, (2) lock washers, and
(2) nuts supplied. Note that the brass spacers
are placed between the bottom of the Trip Unit
and the Mounting Platform and that the 4.00"
screws are inserted through the Trip Unit
Mounting Platform first.
Attached the new PT Module Warning Label
over the existing label in the orientation shown
in Fig. 22.
Fig. 21 PT Module Installed on the Aux. CT
Module
Fig. 22 Correct Orientation of the PT Module
Warning Label
C. Align the Aux. CT Module and the two (2)
Spacer Plates, as shown, with the holes in the
Aux. CT Module Mounting Brackets. Secure
the Aux. CT Module and the spacer plates to
the Mounting Brackets using the (4)
.190-32 × .500" flat head screws, (4) lock
washers, (4) flat washers, and (4) nuts supplied.
Fig. 23 Spacer Placement and Mounting of the
Aux. CT Module
SPACER (1 ON
EACH SIDE)