MPC 50 ATD-313186 Automobile Parts User Manual


 
ATD 50 Actuator
®
Operating Instructions
Page 11
3811 N. Holton Street • Milwaukee, WI • 53212 •USA • Phone • 414-906-4000 • Fax 414-906-4100 • www.MPCovers.com
5.2 Start-up
Check the main power voltage selection switch for proper supply voltage (230V /
115V)
Check the control connections and verify they are correctly installed
Beware of Electrical Voltages!
Switch on the main power supply to the drive.
Start the calibration run (see section below).
Check and test all functions to be used.
If required, re-adjust door-specific parameters (opening and closing speeds,
braking distance, etc.) using the SERsoft programming software.
Test the complete system.
6 Check List for Functional Tests
During the functional tests the door travel path must be free of obstructions. The only
limits to door travel should be the two end-stops. Test the unit according to the
following steps:
TEST 1: POWER-UP
ACTION: Energize the main power to the ATD 50 Actuator
®
EXPECTED BEHAVIOR: No door movement.
Green LED on the Control Board illuminates.
Door is freely moveable.
No errors displayed on LED’ at terminals D5 - D9 (if
installed).
No errors displayed in the SERsoft Diagnostic Display.
TEST 2: CALIBRATION RUN
ACTION: Apply momentary or maintained contact between OPEN
input (A2) and Ground (A1).
EXPECTED BEHAVIOR: Door moves slowly to open position and pushes against
end-stop.
Open position is now set in the microprocessor.
ACTION: Apply momentary or maintained contact of CLOSE input
(A7) and Ground (A1).
EXPECTED BEHAVIOR: Door moves slowly to closed position and pushes
against end-stop.
Closed position is now set in the microprocessor.