Linear LRA Automobile Electronics User Manual


 
LRA Linear Residential Actuator Installation Guide - 13 - 228158 Revision X13 2-3-2009
Advanced Controller Programming
Entering Advanced Programming Mode
To access and program the Advanced Programming functions, for each
programming session, Advanced Programming must be enabled.
After exiting programming, the Advanced Programming functions
will be available on the programming display during the next
programming session unless the operator has run 50 or more
cycles. After that, Advanced Programming must be enabled again.
Maximum Run Time
The factory default for the Maximum Run Time is 99 seconds. When the
operator starts, a timer will begin counting. If a open or close limit is not
reached or an obstacle or reversing input is not received before the timer
expires, the operator will stop, the unit locks out and the alarm sounds.
The timer can be set for 10 to 99 seconds, but should be left at 99 in most
applications. Setting it too close to the actual run time may cause the time
to expire with changing ambient temperature, gate conditions, etc…
Single Button Input Setup
This function is used for selecting the operation for single button controls
and radio receivers.
The factory default sets the SINGLE input terminal so successive inputs
will cycle the operator in OPEN-STOP-CLOSE-STOP order.
Alternately, the SINGLE input can be set to cause the gate to OPEN
unless the gate is fully open. If the gate is fully open, the input will cause
the gate to CLOSE.
Stagger Mode
This function is used in dual gate installations only. The factory
default sets the Stagger Mode to OFF. In dual gate installations the
two operators communicate through the 3-wire COMM LINK interface.
When using the Stagger Mode, set one operator for delayed opening and
the other operator for delayed closing. The Stagger Time programming
function (see below) sets the length of the delay.
NOTE: This function will only be displayed if dual gate operation is
selected.
Stagger Delay Time
This function is used in dual gate installations only. The factory
default sets the Stagger Time to 0 seconds (OFF). The Stagger Time
sets the delay for the Stagger Mode. The Stagger Delay Time can be set
from 1-99 seconds.
NOTE: This function will only be displayed if dual gate operation is
selected.
FUNCTION
ADVANCED PROGRAMMING FUNCTIONS
WILL NOT BE DISPLAYED
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
ADVANCED
PROGRAMMING
"AD"
ADVANCED PROGRAMMING OPTIONS
WILL BE DISPLAYED
NOTE: ADVANCED PROGRAMMING
WILL STAY ENABLED AFTER
EXITING PROGRAMMING UNTIL
THE GATE CYCLES 50 TIMES
FUNCTION
SINGLE INPUT WILL OPEN OPERATOR,
IF OPERATOR IS ALREADY OPEN, SINGLE
INPUT WILL CLOSE OPERATOR
SINGLE INPUT WILL CYCLE OPERATOR
IN ORDER OF OPEN-STOP-CLOSE-STOP
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
SINGLE BUTTON
INPUT SETUP
"SB"
FUNCTION
SETS THIS OPERATOR FOR
DELAYED OPEN
DISABLES STAGGER FUNCTION
SETS THIS OPERATOR FOR
DELAYED CLOSE
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
STAGGER
MODE
"SM"
DUAL GATES
ONLY
FUNCTION
SET STAGGER DELAY VALUE
1 TO 99 SECONDS
STAGGER TIMER DISABLED
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
STAGGER
DELAY TIME
"ST"
DUAL GATES
ONLY
FUNCTION
PRESS ENTER FOR 1 SECOND
WHILE DISPLAY IS FLASHING, PRESS
UP OR DOWN TO CHANGE THE
MAXIMUM RUN TIME (10-99 SECONDS)
OPTIONS
MAXIMUM RUN
TIMER
DISPLAY SHOWS CURRENT
MAXIMUM RUN TIME SETTING
ENTER
ENTER
PRESS ENTER TO STORE THE VALUE
"RT"