Revision 6 HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 69
7/07
Table 25 Input Calibration Procedure
Step Operation Press Result
1
Enter Calibration
Mode
SETUP
until you see
Upper Display =
CAL
Lower Display =
INPUT
FUNCTION Upper Display = DIS
Lower Display =
CAL IN
or key
Upper Display =
BEGN
Lower Display =
CAL IN
2 Calibrate Zero (0%) FUNCTION Upper Display = APLY
Lower Display =
INZERO
Adjust the signal source to an output value equal to 0% range
value.
Wait 5 seconds, then go to step 3.
3
Calibrate Span
(100%)
FUNCTION Upper Display =
APLY
Lower Display =
INSPAN
Adjust the signal source to an output value equal to 100%
range value.
Wait 5 seconds, then go to step 4.
4 FUNCTION
Calibration for zero and span input values are now saved. Input
calibration is complete.
NOTE: The display will automatically go to the CAL MOTOR set
up display. See
Table 26. You may also exit calibation mode by
pressing the DISPLAY or SETUP keys.
ATTENTION:
When calibrating the motor to a short stroke range, you must
reset the end-of-travel limit switches. See Setting End-of-Travel
Limit Switches.