Honeywell 2000 Automobile Parts User Manual


 
Set Up and Calibration Procedures
Display Set Up Group
52 HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual Revision 6
7/07
Display Set Up Group
Table 18 lists the parameters and selections availible for the SET DISPLAY group.
Table 18 Display Set Up Group Parameters
Actuator Lower
Display
Prompt
Selections or
Range of Setting
Parameter Definition/PDA HercuLink
®
Prompt
DECMAL
8888
888.8
default = 8888
DECIMAL POINT LOCATION— This selection determines
where the decimal point appears in the display.
None
One Place
Note: Be sure the selection agrees with the value to be
displayed. If display value requires 4 whole digits, the
decimal will not show.
EUNITS
PCNT
DEG
default = PCNT
UNITS DISPLAY— Selects the units of the position display.
Percent— Shows actuator position as a percentage of span.
(0 to 100%)
Degrees— Shows the actuator position in degrees of
rotation. (0 to 150
°) (90°)
UNITS
SI
ENGL
default = ENGL
DISPLAY UNITS— Selects standard for unit values for the
local display.
SI— Display will show unit values in international (metric)
units. (Temperature in degrees C, Date format: ddmmyy)
English Display will show unit values in U.S. units.
(Temperature in degrees F, Date format: mmddyy)