Power Distribution
© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_work\pcr-m1-rack-um-en\pcrm1-rack-um-en.k07
7.3.5.3 Installation options for 600 mm wide symmetrical racks
Performing the task
Ê Install the socket strips onto the PDU kit 3 HU as described on page 71.
Figure 59: Single-phase 8-way 10 A socket strip mounted in a 600 mm wide symmetrical rack
Ê Install the PDU kit 3 HU into the rack on the desired height.
I The PDU kit 3 HU has to be installed from HU 7 upwards.
Rack height Installation direction vertically Installation direction horizontally
42 HU Not possible
Max. 4x with PDU kit 3 HU
24 HU Not possible
Max. 4x with PDU kit 3 HU
16 HU Not possible
Max. 4x with PDU kit 3 HU
Table 15: Installation options for 600 mm wide symmetrical racks