84
Power Distribution
© cognitas. Gesellschft für Technik-Dokumentation mbH 2011 Pfad: O:\FTS\PRIMERGY-HW\Rack\PCR-M1-Rack\Manuals\User Manual\02_work\pcr-m1-rack-um-en\pcrm1-rack-um-en.k07
Ê Install the socket strip with 2 screws onto the PDU brackets.
I Installation is possible on both sides.
7.3.3.3 Installation options for 600 mm wide symmetrical racks
Performing the task
Ê Install the socket strip onto the socket strip RMK 2U horizontal as described
on page 71.
Figure 52: 32 A three-phase 15-way socket strip mounted in a 600 mm wide symmetrical rack
Ê Install the PDU kit 3 HU in the required height into the rack.
I The PDU kit 3 HU may only be mounted from HU 7 upwards.
Rack height Installation direction vertically Installation direction horizontally
42 HU Not possible
Max. 2x with PDU kit 3 HU
24 HU Not possible
Max. 2x with PDU kit 3 HU
16 HU Not possible
Max. 2x with PDU kit 3 HU
Table 10: Installation options for 600 mm wide symmetrical racks