Software Parameters, cont'd
Parameter
Description
Value Range
(units)
Factory
Settings
User
Settings
Alarm Output #1 Configuration
40 Activation Conditions 0 – Always Off
1 – Always On
2 – Active when Above
3 – Active when Below
4 – Active inside Range
5 – Active outside Range
0
41 Output Style & Reset Mode 1 – Constant & Auto Reset
2 – Constant & Manual Reset
3 – Pulsed & Auto Reset
4 – Pulsed & Manual Reset
1
42 Reset Configuration 1 – No Sil., Reset on Key
2 – No Sil., Reset on S2 High
3 – No Sil., Reset on S2 Low
4 – Sil., Reset on Key
5 – Sil., Reset on S2 High
6 – Sil., Reset on S2 Low
1
43 Display Flash On Active Alarm 0 – Alarm Flash Disabled
1 – Alarm Flash Enabled
0
44 Pulse on Time 1 – 3600 (seconds) 1
45 Pulse off Time 1 – 3600 (seconds) 1
46 Pulse Count 0 – 9999 (pulses) 0
47 Lower Limit 0 – 9999 (display units) 0
48 Upper Limit 0 – 9999 (display units) 9999
Alarm Output #2 Configuration
50 Activation Conditions 0 – Always Off
1 – Always On
2 – Active when Above
3 – Active when Below
4 – Active inside Range
5 – Active outside Range
0
51 Output Style 1 – Constant & Auto Reset
2 – Constant & Manual Reset
3 – Pulsed & Auto Reset
4 – Pulsed & Manual Reset
1
52 Reset Configuration 1 – No Sil., Reset on Key
2 – No Sil., Reset on S2 High
3 – No Sil., Reset on S2 Low
4 – Sil., Reset on Key
5 – Sil., Reset on S2 High
6 – Sil., Reset on S2 Low
1
53 Display Flash On Active Alarm 0 – Alarm Flash Disabled
1 – Alarm Flash Enabled
0
54 Pulse On Time 1 – 3600 (seconds) 1
55 Pulse Off Time 1 – 3600 (seconds) 1
56 Pulse Count 0 – 9999 (pulses) 0
57 Lower Limit 0 – 9999 (display units) 0
58 Upper Limit 0 – 9999 (display units) 9999
Parameter Memory Commands
95 Restore to Factory Settings 0 – Do Nothing & Exit
5 – Restore Factory Settings
0
98 Save to User Setting Area 0 – Do Nothing & Exit
5 – Save Setting
0
99 Restore from User Setting Area 0 – Do Nothing & Exit
1 – Restore Settings
0