2-10 Installation and Operation 5707070-A
Advanced Energy
®
3. Place the transducers side by side between 7 o’clock and 10 o’clock on the pipe
as shown in Figure 2-4. Place the transducers flush to the pipe, facing the same
direction. See Figure 2-5 for an example.
Note: Be careful with transducer placement. Air bubbles near the top of the pipe
or sediment on the bottom of the pipe can hinder successful flow readings.
Place the transducers as shown in Figure 2-4.
Figure 2-4. Clamp-on transducer placement
4. Use the supplied chain and bungee cord to strap the transducers in place, securing
them tightly to the pipe. Figure 2-5 provides an example of two properly mounted
clamp-on transducers.
Transducers
Cross-section of pipe
with mounted
transducers
Electronics enclosure
12 o’clock position
6 o’clock position