Sanyo TH4242 Automobile Accessories User Manual


 
44
44
4
U
36
S4359146
3-23. Suspending the Indoor Unit
Depending on the ceiling type:
Insert suspension bolts as shown in Fig. 3-74
or
Use existing ceiling supports or construct a
suitable support as shown in Fig. 3-75.
It is important that you use
extreme care in supporting
the indoor unit inside the
ceiling. Ensure that the
ceiling is strong enough to
support the weight of the
unit. Before hanging the unit,
test the strength of each
attached suspension bolt.
(1) When placing the unit inside the ceiling, deter-
mine the pitch of the suspension bolts referring to
the dimensional data on the previous page.
(Fig. 3-73)
Tubing must be laid and connected inside the
ceiling when suspending the unit. If the ceiling is
already constructed, lay the tubing into position
for connection to the unit before placing the unit
inside the ceiling.
(2) Screw in the suspension bolts allowing them to
protrude from the ceiling as shown in Fig. 3-74.
(Cut the ceiling material, if necessary.)
(3) Thread the 2 hexagonal nuts and washers (field
supply) onto the 4 suspension bolts as shown in
Figs. 3-76 and 3-77. Use 2 sets of nuts and
washers (upper and lower), so that the unit will
not fall off the suspension lugs.
Fig. 3-76
Fig. 3-74
Fig. 3-75
Fig. 3-77
Hole-in-anchor
Hole-in-plug
Concrete Insert
Suspension bolt (M10 or 3/8")
(field supply)
0038_T_I
Ceiling tiles
Ceiling support
0039_S_I
0041_X_I
Nuts and washers
(2 sets)
Suspension bolt
Suspension lug
Upper
Lower
Suspension bolt
Hexagonal nut
0784_U_I