CMC electronic MAI085MB Automobile Parts User Manual


 
mAI085-MB Actuator Interface Technical Manual /20
Distributive Intelligence
CMC INDUSTRIAL ELECTRONICS LTD
Display
Function Response
GEt
Get the operational parameters from this controller. A YES response
displays SUrE in the lower display. The second YES response starts
the operation. Once complete, the lower display shows DonE.
Should the controller not respond, the lower display will show FAiL..
***************************** WARNING ********************************
This function will overwrite the Interface’s saved copy of the
parameters. Verify the parameters in the actuator controllers
are correct before executing this function.
***************************************************************************
YES/no
Snd
Send the operational parameters to this controller. A YES response
displays SUrE in the lower display. The second YES response starts
the operation. Once complete, the lower display shows DonE.
Should the controller not respond, the lower display will show FAiL.
***************************** WARNING ********************************
This function will overwrite the actuator controllers saved
parameters. This may cause unpredictable results in this field
device. Verify the parameters in the mAI085-MB are correct
before executing this function.
***************************************************************************
YES/no
CAL
Place the actuator controller in calibrate mode. The actuator
controllers have an automated calibration function. This function sets
the primary operational parameters for the controller by exercising
the actuator. A YES response displays SUrE in the lower display.
The second YES response starts the operation. During the
calibration sequence, the lower display shows rUn. Pressing YES will
stop the calibration sequence. The lower display will show DonE
when the sequence ends. If a calibration does not complete the
lower display will show FAiL. It is recommended that the results of
the field calibration be uploaded to the mAI085-MB using the GEt
command. This will allow the verification of the controller parameters
using the parameter functions of this menu. In addition, by saving
the parameters in the interface, a replacement field device can be
easily reprogrammed to match the replaced device using the Snd
command.
***************************** WARNING *******************************
The field actuator will move during this operation. Be sure field
personnel are notified and that the device is safe to operate
before executing this command.
YES/no