Step Function Action at Interface Action at
Actuator Controller
6
From the Controller Menu, use the
GEt function to upload the calibrated
parameters from controller 1.
Parameters for
controller 1 in the
Interface parameter
table are overwritten
with values from the
actuator controller
no action
7
From the Controller Menu, use the tPL
function to set the values from controller
1 as a template
Parameters for
controller 1 in the
Interface parameter
table are stored in a
temporary template
register
no action
6
Using the Factory Values Menu,
propagate the parameters from
controller 1 to the remaining controllers
within the Interface.
Parameters for
actuator controllers 1-
100 in the Interface’s
parameter table are
overwritten with the
values from the
template
no action
7
From the Main Menu, save the values
using the SAv command. Performing
the SAv now insures that the Interface’s
parameter table will not be lost should
power need to be cycled during the
remaining steps. You may perform a
SAv at any time during system setup.
Parameters are saved
to non-volatile memory
in the Interface
no action
8
From the Main Menu, use the Fnd
function to locate the remaining
controllers on the network. Exit
calibration mode and confirm that all of
the installed actuator controllers are
present on the network. If installed
controllers are not present, check field
address settings and wiring and Fnd
again until all of the controllers are
found.
All active flags are
cleared, then set for
those actuator
controllers located on
the network; controller
1 is always set to
active
no action