ELECTRICAL DATA 558D036-072 (cont)
UNIT
558D
NOMINAL
V-PH-Hz
IFM
TYPE
VOLTAGE
RANGE
COMPR
(each)
OFM IFM
ELECTRIC
HEAT*
POWER SUPPLY
DISCONNECT
SIZE†
Min Max RLA LRA Quantity Hp FLA FLA Nom kW** FLA MCA MOCP†† FLA LRA
060
(5 Ton)
208/230-1-60
Std
187 254 28.3 141 1
1
4
1.4
5.9
42.7/ 42.7 50/ 50 43/ 43
155/155
4.9/ 6.5 23.5/27.1 42.7/ 42.7 50/ 50 43/ 43
6.5/ 8.7 31.4/36.3 46.6/ 52.7 50/ 60 46/ 49
9.8/13.0 46.9/54.2 66.0/ 75.1 70/ 80 64/ 69
13.0/17.4 62.8/72.5 85.9/ 98.0 90/100 82/ 90
15.8/21.0 75.8/87.5 102.2/116.8 110/125 97/107
Alt 8.5
48.3/ 48.3 60/ 60 47/ 47
178/178
4.9/ 6.5 23.5/27.1 48.3/ 48.3 60/ 60 47/ 47
6.5/ 8.7 31.4/36.3 50.3/ 56.3 60/ 60 47/ 52
9.8/13.0 46.9/54.2 69.7/ 78.7 70/ 80 64/ 72
13.0/17.4 62.8/72.5 89.5/101.6 90/110 82/ 93
15.8/21.0 75.8/87.5 105.8/120.4 110/125 97/111
208/230-3-60
Std
187 254 17.7 110 1
1
4
1.4
5.9
29.4/ 29.4 35/ 35 29/ 29
124/124
4.9/ 6.5 13.6/15.6 29.4/ 29.4 35/ 35 29/ 29
7.9/10.5 21.9/25.3 34.7/ 38.9 40/ 40 32/ 36
12.0/16.0 33.4/38.5 49.1/ 55.5 50/ 60 46/ 51
15.8/21.0 43.8/50.5 62.1/ 70.5 70/ 80 57/ 65
19.9/26.5 55.2/63.8 76.4/ 87.1 80/ 90 70/ 80
Alt 8.5
32.0/ 32.0 40/ 40 29/ 29
145/145
4.9/ 6.5 13.6/15.6 32.0/ 32.0 40/ 40 29/ 29
7.9/10.5 21.9/25.3 38.0/ 42.2 45/ 45 32/ 36
12.0/16.0 33.4/38.5 52.3/ 58.7 60/ 60 45/ 51
15.8/21.0 43.8/50.5 65.3/ 73.8 70/ 80 57/ 65
19.9/26.5 55.2/63.8 79.7/ 90.3 80/100 70/ 80
460-3-60
Std
414 508 8.6 55 1
1
4
0.8
3.2
14.8 20 15
63
6.0 7.2 14.8 20 15
11.5 13.8 21.3 25 20
14.0 16.8 25.0 30 23
23.0 27.7 38.6 40 36
25.0 30.1 41.6 45 38
Alt 4.5
16.1 20 14
73
6.0 7.2 16.1 20 14
11.5 13.8 22.9 25 19
14.0 16.8 26.7 30 22
23.0 27.7 40.2 45 35
25.0 30.1 43.2 45 38
575-3-60
Std
518 632 6.4 44 1
1
4
0.8
3.2 12.0 15 12 52
Alt 2.6 11.4 15 12 62
072
(6 Ton)
208/230-
3-60
Std 187 254 20.9 142 1
1
4
1.4 5.8
33.3/ 33.3 40/ 40 32/ 32
187/187
4.9/ 6.5 13.6/15.6 33.3/ 33.3 40/ 40 32/ 32
7.9/10.5 21.9/25.3 33.3/ 38.8 40/ 40 32/ 36
12.0/16.0 33.4/38.4 48.9/ 55.4 50/ 60 45/ 51
15.8/21.0 43.8/50.5 62.0/ 70.4 70/ 80 57/ 65
19.9/26.5 55.2/63.8 76.8/ 86.9 80/ 90 70/ 80
460-3-60 Std 414 508 9.9 72 1
1
4
0.8 2.6
15.6 20 15
94
6.0 7.2 15.6 20 15
11.5 13.8 20.5 25 19
14.0 16.8 24.3 25 22
23.0 27.8 37.8 40 35
25.5 30.7 41.6 45 38
575-3-60 Std 518 632 7.9 58 1
1
4
0.8 2.6 14.6 15 12 76
LEGEND AND NOTES FOR ELECTRICAL DATA TABLES ON PAGES 49-54
LEGEND
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
IFM Indoor (Evaporator) Fan Motor
LRA Locked RotorAmps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
NEC National Electrical Code
OFM Outdoor (Condenser) Fan Motor
RLA Rated LoadAmps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and
575v.Heaters arerated at240v,480v,and 575v. Ifpower distributionvoltageto unit
varies fromrated heatervoltage, heaterkW willvary accordingly.Todetermine heater
capacity at actual unit voltage, multiply 240 v, 480 v, or 575 v capacity by multipliers
found in Electric Heat Multiplication Factors table on page 48.
†Used to determine minimum disconnect size per NEC.
**Heaters are field installed only.
††Fuse or HACR circuit breaker.
Fusing in single point box provides the required branch circuit protection.
NOTES:
1. IncompliancewithNECrequirementsfor multimotorandcombinationloadequipment
(refertoNECArticles430and 440),theovercurrentprotectivedevice fortheunitshall
be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than
2%.
Use the following formula to determine the percent of voltage imbalance.
max voltage deviation from average voltage
% Voltage Imbalance =100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 −452 = 5 v
(BC) 464 −457=7v
(AC) 457 −455=2v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your
local electric utility company immediately.
3. MCA calculation for 558F180-300 units with electric heaters over 50 kW =
(1.25 x IFM amps) + (1.00 x heater FLA).
036-150 Only 036-072 Only
090-150 Only 180-300 Only 180-300 Only
50