ARI* CAPACITY RATINGS
UNIT 558D
NOMINAL
TONS
STANDARD
CFM
NET COOLING
CAPACITY (Btuh)
TOTAL
kW
SEER†
EER
SOUND
RATING
(Bels)
Belt Drive Direct Drive
036 3 1200 35,000 4.0 10.0 9.7 8.7 8.2
048 4 1600 47,000 5.5 10.0 9.7 8.6 8.2
060 5 2000 57,500 6.7 10.0 9.7 8.5 8.2
UNIT
NOMINAL
TONS
STANDARD
CFM
NET COOLING
CAPACITY (Btuh)
TOTAL
kW
EER IPLV
SOUND
RATING
(Bels)
558D072 6 2100 70,000 7.9 8.9 ** 8.4
558D090 7
1
⁄
2
2800 86,000 9.6 8.9 9.35 8.6
558D102 8
1
⁄
2
3000 98,000 11.0 9.0 9.00 8.6
558D120 10 4000 117,000 13.0 9.0 9.35 8.8
558D150 12
1
⁄
2
4500 142,000 15.8 9.2 9.65 8.8
559F180 15 5250 178,000 20.7 8.6 10.70 8.8
559F216 18 6000 190,000 21.3 8.9 9.20 9.0
559F240 20 6200 222,000 25.5 8.7 8.80 9.5
559F300 25 7200 268,000 31.2 8.6 8.40 9.5
LEGEND
Bels — Sound Levels (1 bel = 10 decibels)
EER — Energy Efficiency Ratio
IPLV — Integrated Part-Load Values
SEER — Seasonal Energy Efficiency Ratio
*Air Conditioning and Refrigeration Institute.
†Applies only to units with capacity of 65,000 Btuh or less.
**The IPLV applies only to 2-stage cooling units.
NOTES:
1. Rated in accordance with ARI Standards 210/240-89 (unit sizes 036-120) or 360-86 (unit sizes 150-240) and 270-84.
2. Ratings are net values, reflecting the effects of circulating fanheat. The 300 size is beyond the scope of the ARI certification
program.
3. Ratings are based on:
Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F db air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature.
SIZES 036-150 SIZES 180-300
5