![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/3/bb/3bbbceb2-10c6-4f24-8f7c-b05ba99ff31c/3bbbceb2-10c6-4f24-8f7c-b05ba99ff31c-bg10c.png)
Chapter 7
7-
33
ADAM 4000 Series User’s Manual
$AAM
Name Read Module Name command
Description The command requests the counter/frequency module at
address AA to return its name
Syntax $AAM (cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address that you will access to.
M is the Read Module Name command.
(cr) is the terminating character, carriage return (0Dh).
Response !AA(Module Name)(cr) if the command is valid.
There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.
! is a delimiter character which indicates a valid command.
AA (range 00-FF) represents the 2-character hexadecimal
address of the module.
(Module Name) is the name of the module at address AA.
For example, 4080D
(cr) is the terminating character, carriage return (0Dh).
4080, 4080D