![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/3/bb/3bbbceb2-10c6-4f24-8f7c-b05ba99ff31c/3bbbceb2-10c6-4f24-8f7c-b05ba99ff31c-bg95.png)
Chapter 5
5-3
ADAM 4000 Series User’s Manual
Command
S
ntax
Command Description I/O Module
$AA4 Returns the value that was
stored in the specified module's
register after the #** command
4011, 4011D, 4012, 4013, 4015,
4015T, 4016
$AAB Ask the module to respond
whether the wiring is open or
closed
4011D, 4015, 4015T, 4018+,
4019+
$AA3 Returns the value of the CJC
sensor for a specified analog
input module
4011, 4011D, 4018, 4018+,
4018M, 4019+
$AA9 Calibrates the CJC sensor for
offset errors
4011, 4011D, 4018, 4018+, 4018M
4019+
$AA0Ci Calibrates a specified channel
to correct for
ain errors
4015, 4015T, 4017+, 4018+, 4019+
$AA1Ci Calibrates a specified channel
to correct for offset errors
4015, 4015T, 4017+, 4018+, 4019+
$AA7CiRrr Configure the input type and
range of the specified channel
in an analo
input module
4015, 4015T, 4017+, 4018+, 4019+
$AA8Ci Get the input type and range of
the specified channel in an
analo
input module
4015, 4015T, 4017+, 4018+, 4019+
$AAXnnnn
Communication Watchdog Timer
Setting
4015, 4015T, 4017+, 4018+,4019+
$AAY
Read Communication Watchdog
Timer Setting
4015, 4015T, 4017+, 4018+, 4019+
$AAS0 Internal self-calibration for offset
and
ain errors
4015, 4015T
$AAS1 Reload factory default
calibrating parameter to
overwrite current calibrating
parameter
4015, 4015T