7-9. Electrical Wiring
Connection method
(1) Connect W1 to the indoor PCB WL connector.
(2) Connect W3 from the indicator section with W2
from the operating controller using the relay
connector.
7-10. Test Run Switch
Test run switch is located at operating control unit.
Regarding the test run, please refer to section 12. Test
Run.
● In case of 4-way air discharge type, test run opera-
tion is not possible without the ceiling panel installa-
tion.
● During the test run, all of the 3 indicator lamps on
the indoor unit will flash.
● During the test run, the air conditioner runs continu-
ously and the thermostat does not control the
system.
● To protect the air conditioner from overloading, the
outdoor unit will not start running for 3 minutes after
power is applied or the air conditioner is turned off
and then back on.
● When the air conditioner fails to start the test run, 1
or more of the 3 alarm indicator lamps on the indoor
unit will flash (See next section).