Quick Start Guide for Herculine 2000 Series
Group
Prompt
Function
Prompt
Value or
Selection
Factory
Setting
RELAYn
RTYP NONE
RnyE X1
RnyVAL 0.0
RnyHL LO
RLYnHY 0.0
CU OUT
CUROUT NONE
Depends on
MSG
COMM
COMM DIS
ADDRES 1
BAUD 19.2
XmtDLY 20ms
DBLBYT FP B
DIGINP
DIGINP NONE
EndPos 0
DISPLA
DECMAL 8888
EUNITS PCNT
UNITS ENGL
LOCK
LOCKID 0
LOCK NONE
MAENAB ENAB
STATUS
FAILSF Read Only Read Only
RAMTST Read Only Read Only
SEETST Read Only Read Only
CFGTST Read Only Read Only
CALTST Read Only Read Only
DRVINF
VERSON Read Only Read Only
SPEED Read Only Read Only
POWER Read Only Read Only
ROTATE Read Only Read Only
TAG 6 alpha
characters
MFGDAT Read Only Read Only
LREP Factory Set Factory Set
LCAL Factory Set Factory Set
REPTYP Factory Set Factory Set
Group
Prompt
Function
Prompt
Value or
Selection
Factory
Setting
MAINT
TEMP NONE
TEMPHI X1
TEMPLO 0.0
hh:mm:ss ACST Read Only
STARTS Read Only Accumulated
Motor Starts
RnCNT
n=1,2,3,or4
Read Only Relay Cycle
Counts
REGNn
n= 0 to 9
Read Only Accumulated
Motor Starts
TOTDEG Read Only Total Degrees of
Motor Travel
DATSAV DIS
PASSWRD Nnnn
MANRST NONE
LD CAL NONE
LD CFG DIS
RESTRT DIS
7. Start up/Operation
After the actuator is completely installed, wired, and
the preliminary adjustments made, check the
operation of the actuator and controlled device
before placing it in service. Operate the controlled
device and check its direction of travel in response
to an increase of the input signal and make sure it is
correct for the process. Actuators having the
optional auto-manual switch must have the knob set
in the AUTO position.
When power is applied to the actuator, the actuator
electronics performs a diagnostic routine on various
device components. These tests include a:
RAM diagnostic (RAMTST),
Check of the electrically eraseable PROM
(SEETST),
Verification that valid parameter values are
in the actuator configuration (CFGTST),
Verification of valid calibration values
(CALTST)
Test of the local display and LED indicators
(all display segments and LED indicators
light simultaneously).
The optional local display shows the status of the
diagnostics as they are completed during power up.
TEST DONE is shown on the display when
diagnostics are complete and actuator should be in
AUTO mode.
If the Actuator Motor is “Hunting” (Motor does not
drive to a position and stop) the process control
loop is not tuned correctly. Refer to the Instruction
Manual for your controller on how to tune a loop.