Omega FD6001 Automobile Parts User Manual


 
3-20
PART 3 - TROUBLE SHOOTING
CONDITION POSSIBLE CAUSE
Unit does not turn “ON” when power is
applied
Verify that AC power source is live.
Test the fuse
Verify that proper power supply jumpers
are in place.
FAULT CONDITION is indicated on LCD
indicator
Fault conditions can arise from several
causes: electrical surges, short circuits,
open circuits, etc. To clear a “Fault Condi-
tion”, press
2nd Function
then press
Re-
set
. Use the arrow keys to change the
Fault code number to “
0
”. Press
Enter
. If
the meter resumes measuring flow, no
permanent damage was incurred.
Ensure that the transducer is properly
mounted to the pipe.
Verify that transducer connections are
correct
Ensure that the pipe is full of moving
liquid.
If SIGNAL STR is less than 000100 counts
and flow rate is greater than 1 FPS [0.3
MPS], adjust GAIN control (R13 on the
Main PCB) till SIGNAL STR reaches at
least 000125 counts.
On cleaner liquids, move the transducers
closer to a 90
o
pipe elbow.
If GND connection and pipe are at
different potentials, ground FD6000 to
pipe potential.
If Variable Frequency Drives are being
utilized, verify that the FD6000 obtains a
flow indication when the pump turns OFF.
If it does, contact OMEGA Engineering.