Multiquip DCA220SSJ/SSJU Automobile Parts User Manual


 
PAGE 56 — DCA-220SSJ/SSJU — OPERATION AND PARTS MANUAL — REV. #0 (02/04/14)
Normal Shutdown Procedure
To shutdown the generator use the following procedure:
1. Place both the MAIN, GFCI and LOAD circuit breakers
as shown in Figure 39 to the OFF position.
2. Place the engine speed switch (Figure 56) in the “
LOW
(down) position.
Figure 57. MPEC Control Switch (Off/Reset)
5. Verify that the
all
status LED on the MPEC display
are OFF (not lit).
6. Remove all loads from the generator.
7. Inspect entire generator for any damage or loosening of
components that may have occured during operation.
Emergency Shutdown Procedure
1. To shut-down the engine in the event of an emergency,
push the
Emergency Stop Button
(Figure 58).
2. Switch the
MAIN
,
GFCI
and
LOAD
(Figure 38) circuit
breakers to OFF position.
DCA-220SSJ/SSJU — GENERATOR SHUT-DOWN PROCEDURES
3. Let the engine cool by running it at low speed for 3-5
minutes with no load applied.
4. Place the
MPEC Control Switch
(Figure 57) to the
OFF/RESET position.
Figure 56. Engine Speed Switch (Low)
NEVER stop the engine suddenly except in an emergency.
WARNING -
SHUTTING DOWN THE GENERATOR
Figure 58. Emergency Stop Button
ALWAYS make sure the diagnostic switch is placed in the
OFF position before attempting to shut down the generator.
The OFF/RESET switch on the MEC controller will not
shut down the generator if the diagnostic switch is left in
the ON position.
CAUTION -
DIAGNOSTIC SWITCH