Multiquip DCA220SSJ/SSJU Automobile Parts User Manual


 
PAGE 38 — DCA-220SSJ/SSJU — OPERATION AND PARTS MANUAL — REV. #0 (02/04/14)
Figure 8. Engine Operating Panel
DCA-220SSJ/SSJU — ENGINE OPERATING PANEL
The definitions below describe the controls and functions of
the DCA-220SSJ/SSJU
Engine Operating Panel
(Figure 8).
1. Panel Light – Normally used in dark areas or at night
time. When activated, panel lights will illuminate. When
the generator is not in use be sure to turn the panel
light switch to the OFF position.
2. Panel Light Switch – When activated will turn on control
panel light.
3. Oil Pressure Gauge – During normal operation this
gauge be should read between 35 to 65 psi. (241~448
kPa). When starting the generator the oil pressure may
read a little higher, but after the engine warms up the oil
pressure should return to the correct pressure range.
4. Water Temperature Gauge – During normal operation
this gauge be should read between 180° and 230°F. (82° C
and 110° C
5. Charging Ammeter Gauge – Indicates the current
being supplied by the engine’s alternator which provides
current for generator’s control circuits and battery
charging system.
6. Fuel Gauge - Indicates amount of diesel fuel available.
7. Tachometer – Indicates engine speed in RPM’s for 60
Hz operation. This meter should indicate 1800 RPM’s
when the rated load is applied. In addition a built in hour
meter will record the number of operational hours that
the generator has been in use.