Chapter 3: Main Menu and SubMenus
To access the RCM8 Main Menu VIA MODEM:
1. Make sure RCM8 and attached modem are turned on and
properly configured.
2. On the remote PC, set up terminal emulation session for
dial-out access – Connect Using an attached modem, rather
than direct connect to a com port.
3. Once a connection has been established with the RCM8,
press Space Bar to initiate the log-in process.
4. Type the RCM8 password, then press Enter to gain access to
the RCM8. The factory-default password for modem access
is also “RCM8”.
5. From here, continue to Step 3 of the local login process.
Configuration
The Configuration option from the Main Menu lets you view the
current RCM8 settings.
1. Press 1 to display the Configuration menu:
RCM8 V4.0 CONFIGURATION - MON 07-05-99 18:03:20
SITE ID = WEST WING COMPUTER ROOM PAGER ID - 5551149
IN DELAY NO DIAL ALT DIAL MESSAGE
MM:SS NC A CODE B
-------------------------------------------
01 00:00 NO 1 0 0 WATER UNDER FLOOR
02 00:00 NO 1 0 0 HIGH TEMP
03 05:00 NC 2 & 1 DOOR HELD OPEN
04 00:00 NO 0 0 0 CLOGGED FILTER
05 00:00 NO 0 0 0 HIGH HUMIDITY
06 00:00 NO 0 0 0 CONTACT #6
07 00:00 NO 0 0 0 CONTACT #7
08 00:00 NO 0 0 0 CONTACT #8
RCM8 Phone Number =
Phone Number 1 = 9,5551212,,,,,911##
Phone Number 2 = A9,18007596366
Dial Prefix = ATE1X4DT
Redial Tries = 2
Redial Interval = 30
Modem = CONNECTED
Modem Baud Rate = 1200
EIA-485 Online Units =
This is a view-only screen. Use the remaining Main Menu
options to make changes or reset the values shown in this
screen.
2. Press Esc to return to the Main Menu.
Liebert RCM8 17