Honeywell W7751H Automobile Parts User Manual


 
EXCEL 10 W7751H SMART VAV ACTUATOR
11 95-7553—04
Fig. 20. W7751H to PWM Valve Actuator and series or parallel fan.
Fig. 21. W7751H to pneumatic transducer.
12345678 910
11
12
24 VAC
COM
OUT 1
OUT 2
E-BUS
24 VAC
W7751H
M10529
WALL MODULE
EARTH
GND
SENSOR
BYPASS
LED
NOT EARTH GROUND
TRIAC
EQUIVALENT
CIRCUIT
2
1
1
2
MAKE SURE ALL TRANSFORMER/POWER WIRING IS AS SHOWN; REVERSING TERMINATIONS WILL RESULT IN EQUIPMENT MALFUNCTION.
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTING INTO THE TERMINAL BLOCK.
ML7984B
REHEAT
VALVE
ACTUATOR
PWM OUTPUT
FROM CNTRL
PWM (H 24 VAC)
PWM VALVE ACTUATOR
24 (N)
?24 (H)
T6 T5 C B W R
SERIES OR
PARALLEL
FAN
CONTACTOR
(24 VAC)
SET PT
12345678 910
11
12
24 VAC
COM
OUT 1
OUT 2
E-BUS
24 VAC
W7751H
M10530
WALL MODULE
EARTH
GND
SENSOR
BYPASS
LED
NOT EARTH GROUND
TRIAC
EQUIVALENT
CIRCUIT
3
2
4
1
1
2
3
4
REVERSE WIRES (INCREASE/DECREASE) TO REVERSE ACTION (DIRECT/REVERSE).
MAKE SURE ALL TRANSFORMER/POWER WIRING IS AS SHOWN; REVERSING TERMINATIONS WILL RESULT IN EQUIPMENT MALFUNCTION.
OPTIONAL 24 VAC WIRING TO NEXT CONTROLLER.
USE 1/4 IN. (6 MM) MINIMUM PNEUMATIC TUBING. BRANCH LINE MUST BE 6 FT (1.8M) OR LONGER.
PNEUMATIC
VALVE
MMC325 PNEUMATIC
TRANSDUCER
24 (N)
24 (H)
DECREASE
INCREASE
24 (N)
?24 (H)
M
M
B
SET PT